BAUDER VIP

VACUUM INSULATION PANEL

Bauder VIP is a vacuum insulation panel designed to provide high thermal performance in areas with limited insulation height and is ideally suited for terrace and balcony applications.

The exceptional insulating properties (calculated value of thermal conductivity λ = 0.0063 W/mK) achieved by BauderVIP is due to the high performance vacuum silica core. This silica is encased by a multi-layer composite aluminium foil, and then the air is removed from the silica to create a vacuum.

In order to protect the vacuum during installation and against normal construction processes, Bauder VIP is protected on the underside with a 3mm thick rubber granulate mat and on the upper surface with 17mm Bauder PIR. Both protective layers are bonded to the vacuum core to provide one complete encapsulated panel.

VIP insulation panels are 60mm thick and can be used in conjunction with other Bauder insulation boards to enhance U values if required.

Page2_1

Page2_2

Delivery and Storage

When delivered, check that all panels are present according to the roof plan and ensure panels have not suffered any visible damage in transit. Damaged panels must be recorded on the delivery note and replaced if necessary.

The panels are delivered flat on a pallet with protection and should be stored this way on site. Do not store VIP boards standing upright. Protect panels from moisture prior to installation.

Suitable Deck and Vapour Barrier

Concrete or timber decks are suitable, provided structural requirements of the landscaping are met. The deck should be clean, dry and free from any protrusion which could damage the waterproofing system.

Bauder primer should be applied, as directed in the technical literature, and once dry the Bauder vapour barrier can be installed in accordance with Bauder technical installation instructions.

VIP INSTALLATION

Panel Installation

BauderVIP panels are installed according to the roof plan directly on to the vapour barrier with the PIR surface of the panel facing up and the underside of rubber granulate in direct contact with the vapour barrier. The panels must be bonded to the vapour barrier with Bauder Insulation Adhesive in accordance with Bauder technical installation instructions.

Lay boards, butt jointed and staggered, over the entire roof surface as per the roof plan drawing and install cut Bauder FA-TE with Bauder Insulation Adhesive around the perimeter to infill any sections that are not complete.

If an additional layer of insulation is required due to U-value requirements, Bauder PIR, Bauder FA-TE, Bauder EPS or Bauder Tapered insulation should be adhered to the upper surface of the VIP panel with Bauder Insulation Adhesive. The two layers of insulation types should be staggered to ensure no vertical joints are aligned.

⚠️ Warning
Before installing the Bauder VIP, the vapour barrier must be thoroughly clean and free of stones or metal chips that could damage the vacuum element. The high barrier tape around the VIP panel must not be damaged or removed.

Product Dimensions

The Bauder VIP 60mm panels are supplied in the following sizes:

  • 1000 x 1000mm
  • 1000 x 500mm
Page3_1

Waterproofing Membrane

If the waterproofing is applied to the top surface of the VIP panel the first layer must be BauderTEC KSA DUO self-adhesive membrane. The capping sheet can be selected from the full Bauder Ltd range of options.

If a second layer of insulation has been installed over the VIP panel an alternative torch applied underlay may be selected from the current Bauder Ltd product offerings.

⚠️ Warning
The VIP core or the board edge with the high-barrier film tape must not be exposed to the naked flame.

Formation of Night Seals with VIP Insulation

At the end of each working day, the new waterproofing should be terminated with a secure and waterproof temporary seal, which can be fully removed the following day. Either self-adhesive or torch-on material can be used to create the seal.

In systems incorporating BauderTEC KSA DUO, it is easiest to use this product to create the night seal. The KSA DUO should be extended on to the flat vapour barrier by a minimum of 200mm from the exposed edge of the VIP insulation or FA-TE infill board and heat activated to ensure a satisfactory seal.

⚠️ Warning
If creating a night seal using torch applied material it is important that the flame does not come into contact with the high barrier tape around the VIP board edge.

To ensure that no moisture contamination of the system can occur between each working period, it is essential that the night seal is properly and securely bonded.

Terrace Construction

Suitable protection must be installed over the completed waterproofing prior to the installation of any surfacing or landscaping.

If despite all the precautions the VIP core is punctured, the compressive strength and the thermal insulation property of the panel will decrease. If punctured the thermal conductivity of the panel becomes 0.020 W/mK.

Page3_2