Blue Roof Flow Restrictor
Pre-Conditions
This guide describes the correct installation of the Bauder Blue Roof Flow Restrictor within a Bauder Insulated Outlet.
It is essential that you read these instructions before installing the Bauder Blue Roof Flow Restrictor and refer to the project specification for the H-Max levels.
Components
Each flow restrictor comprises four parts that are assembled, measured and the overflow pipe cut to meet the specification requirements before finally installing in to the outlet.

- Overflow pipe (chamfered on one end)
- Inner seal
- Base plate (shown here with one flow restrictor hole)
- Outer seal
Setting Up the Flow Restrictor
1.Check each flow restrictor is correct and meets the specification of the particular roof area it is to be fitted on. Every flow restrictor is manufactured with a specific number of restrictor holes to meet the roof area SuDS requirements.
2. Fit the inner and outer seals on the base plate ensuring a tight fit (no snags or lips).
The outer seal has a specific orientation and should be positioned with the sealing ribs uppermost on the base plate.

Completed base plate with inner and outer seals in position.

Positioning the Overflow Pipe and Cutting to the H-Max Height
3. Insert the base plate into the outlet, this should sit 10mm below the surface of the outlet when correctly installed.

4. Lubricate the chamfered end of the overflow pipe and push into the central hole of the baseplate, a stopper within the baseplate sits at 27mm. Ensure the overflow pipe is inserted in to this point.

5. From the specification provided for the project, measure the H-Max from the top of the waterproofing and mark on the overflow, it is advisable to do this at four separate points.

6. Remove the overflow and carefully cut off the excess from the mark you have just made. Care should be taken not to cut the overflow at an angle. Remove burs.

7. Replace the overflow, and confirm measurement, check no debris is blocking any of the restrictor flow holes and install the inspection chamber.