Accessories
Manual Sections
7.1 KS ALU 250 inspection chamber and extension
Boxed access compartment for drainage outlet, fabricated from powder coated aluminium with lockable lid opening.
| Technical data | |
|---|---|
| Size (w x l x h) | 250 x 250 x 100 mm |
| Weight | 950 g |
| Height extenders | 50 mm or 100 mm |
| Support flanges | 100 mm on three sides |
Cutting: In narrow gutters or tight locations, the chamber may need cutting to fit. Modify with tin-snips or hacksaw along perforated slots and file smooth. Use a protection board to avoid damage to the waterproofing or landscaping components.


Installation
- Cut back any PE 02, protection mat, drainage layer or FV 125 from the outlet opening.
- Place the chamber on top of the protection layer, positioned centrally over the outlet.
- On installations without a protection layer, place a small area of protection mat or fleece for the chamber to rest on.
- Do not allow any material to lap up the side of the chamber, as this will block the drainage slots.
- Surround the inspection chamber with 20-40 grade rounded pebbles.

Extension sections
- Remove chamber lid to fit and secure the extension section(s) required.
- Ensure sufficient extension sections have been fitted so that the top of the chamber is flush with the vegetation.
- Replace the lid.

Blue roofs
When used over a blue roof outlet, ensure sufficient extension sections are used to allow 50 mm clearance above the H-Max overflow pipe (see Section 12.4).
Tips:
- The lock on the chamber cover can be undone with a flat-blade screwdriver.
7.2 AL 40 edge trim
1.5-mm aluminium drainage trim and edge restraint for XF 301 sedum blanket.
| Size (h x w x l) | 100 x 80 x 2,000 mm |
| Supply form | 10 lengths per box (20 m) |
| Corners | External corners available individually |

Handling: Drainage trim has sharp edges. Gloves should be worn.
Installation
- Lay out pre-formed 90° corner sections and lengths of AL 40 around perimeter to determine cutting sizes required.
- Measure and cut AL 40 straight, removing any burrs with a hand file.
- Use connector pieces at joints so AL 40 trim runs straight and true.
- Fix each length to the waterproofing using strips of 200 mm x 500 mm cap sheet at 400-mm intervals.

Tips:
- Where possible, avoid running on top of waterproof laps or joints when positioning AL 40.
- To work out the best fixing position, assemble sections with connectors and corners before fixing.
- Ensure a secure bond through the holes in the AL 40.
- See Section 6.1 for XF 301 sedum blanket installation.

7.3 KFL AL 100/80 edge trim
1.5-mm aluminium drainage trim, open-edge restraint or gutter detail which can be used to provide either an 80-mm or 100-mm face.
| Size (h x w x l) | 80 x 100 x 2,500 mm |
| Supply form | Nominated quantity |

Installation
- Lay out lengths of KFL AL 100/80 around perimeter to determine cutting/sizes required.
- Measure and cut KFL AL 100/80 straight, removing any burrs with a hand file
- Ensure KFL AL 100/80 trim runs straight and true.

Bituminous systems
Fix each length to the waterproofing using strips of 200 mm x 500 mm of matching membrane or cap sheet, bonded at 400 mm intervals.
Single ply systems
Feed a thin strip of single ply through the pre-cut horizontal slots positioned along the base of the vertical face of the trim and hot air weld to the main waterproofing.
Fixing strips should be at 200 mm intervals.

Note:
KF AL 100/80 cannot be used as a mechanical restraint on pitched roofs.
7.4 AL 150
1.5-mm aluminium drainage/containment trim, open edge restraint or gutter detail.
| Size (h x w x l) | 150 x 146 x 2,500 mm |
| Supply form | Nominated quantity with 1 connector supplied per length |
| Substrate depths | Typically 80-200 mm |

Handling: Drainage trim has sharp edges. Gloves should be worn.
Installation
- Lay out lengths of drainage trim around perimeter to determine cutting/sizes required.
- Measure and cut drainage trim straight, removing any burrs with a hand file.
- Ensure drainage trim runs straight and true.
- Fit connection pieces so the drainage slots are aligned.
- Connection pieces can be bent to form internal/external corners.
- Fix each length to the waterproofing using strips of 250 mm x 500 mm cap sheet, bonded at 400-mm intervals through the foot plate fixing holes.
Matching waterproof membrane strips torch-bonded for bituminous systems:
Use the appropriate membrane to match the system (BTRS or BTRS PLUS), and make a secure torch bond through the holes of the foot plate before completing.
Thermofol or Thermoplan membrane for single ply systems:
Use the appropriate membrane to match the system (Thermofol or Thermoplan). Ensure the membrane is securely heat-welded through the holes of the foot plate before completing.



• Avoid fixing where multiple laps converge. Set back the trim at abutments to avoid angle fillets and detail flashings.
• Only bend connection pieces once to form corners as re-bending will cause them to snap.
• Additional connection pieces should be ordered where required (i.e. detailing around outlets etc).
• For intricate detailing (corners or tight returns), the foot plate can be trimmed to suit.
Note:
Drainage trim cannot be used as a mechanical restraint on pitched roofs.
7.5 RS 22 retention strip
1.2-mm stainless steel mechanical retention strip supplied with protective plastic cover. Used to prevent XF 301 slipping on pitched roofs typically greater than 10° for bituminous systems and greater than 5° for single ply.
| Technical data | Details |
|---|---|
| Size (h x w x l) | 22 x 100 x 800 mm |
| Supply form | 24 lengths per box |
Handling: Gloves should be worn to protect your hands from the sharp edges of the drainage trim.
Quantities: Allow one retention strip per 2-m length of XF 301.


Installation
- If specified, ensure AL 40 has been installed prior to commencing installation of retention strip (see Section 7.2).
- Measure roof area and confirm exact layout of each XF 301 roll (standard and long rolls).
- Each 800-mm-wide retention strip is designed to sit centrally across the width, beneath the 2-m-long long roll of XF 301.
- Create a laying plan for the retention strips that matches that for the XF 301.
- Layout the first retention strips 200 mm from the top edge and 100 mm from the side edge of the roof.
- Position the retention strip with the fixing plate above (uphill) the row of spikes.
- Place at 2-m intervals down the roof.
- Fix each retention strip to the waterproofing using strips of 200 mm x 800 mm membrane securely bonded through the foot plate holes.
Tips
- Minor adjustments (50-100 mm) to the position of the retention strip can be made to avoid a build up of laps.
- Where there are rooflights and other penetrations, the bottom edge of the penetration should be treated as the top edge of the system (i.e. retention strip fitted 200 mm below).
- Do not rest irrigation pipework on the retention strip spikes.


7.6 ER MR 150/60 linear drain
Galvanised steel linear drainage product used around door thresholds and changes in landscape finish. Adjustable support legs accommodate height variations. Installed with connector clips and stop-ends.
| Technical data | Details |
|---|---|
| Size (h x w x l) | 60 x 150 x 1,000 mm |
| Support legs (2 pairs) | Height adjusts 95 - 130 mm |


Installation
- Ensure the roof surface is clean and level and the protection layer is fitted.
- Avoid sitting adjustable feet over welded membrane laps.
- Measure the length of the drainage run required.
- Position linear drain, linking the units with connector clips.
- Cut linear drain if required.
- Fit stop-ends to each end of the drainage run.
- Fit and adjust legs to ensure the drain sits flush with the paving/threshold, etc.
- Ensure two pairs of legs are fitted per 1-m length of linear drain.


7.7 GA MR 250 & 400 access cover
Channel and grille plate made from galvanised steel giving access to rainwater outlets in paved finishes. Can be used in conjunction with BauderGREEN ER MR 150/60 linear drain.

| Technical data | GA MR 250 | GA MR 400 |
|---|---|---|
| Size | 250 x 250 mm | 400 x 400 mm |
| Weight | 3.5 kg | 4.0 kg |
| Height Adjustment | 80-100 mm | |
Installation
- Ensure the roof surface is clean and level.
- Position the access grille directly over the rainwater outlet.
- Grille should be mounted using a Bauder pedestal support system.
- Ensure a protection layer is fitted beneath the pedestals.
Never fit outlet access cover on unstable surfaces, such as green roof drainage layers or water retention products.