Capping Sheets

8 Capping Sheets

Capping SheetApplication
BauderKARATTorch-on
Bauder K5KTorch-on
BauderFLEX K5ETorch-on
BauderFLEX K4ETorch-on
Bauder PYE PV 200 S4Torch-on
BauderTEC KSO-P SNSelf-Adhesive
BauderTEC KSO SNSelf-Adhesive
BauderTEC KSO ALP SNSelf-Adhesive
 
⚠️ Warning

Important:

Cap sheet should run in the same direction as the underlayer, and be off-set from the underlayer, so as not to impede drainage/falls. No small sections should be used.

 

8.1 General guidance for all capping sheets

All laps: Heat sealed to provide a continuous bitumen bead extrusion.

Head laps: 100 mm and staggered by minimum of one metre to the adjacent sheet.

Side laps: 80 mm.

All laps to upstands, edge details, flashings etc: a minimum 100 mm.

Penetrations: Fully seal using bonding methods recommended by Bauder. Please see Bauder bituminous detail drawings.

8.2 Torch-on fully bonded capping sheets

KARAT, K5K, K5E, K4E & PYE PV 200 S4.

Bond: Full over whole surface, with no air pockets.

Laying top layer: Fully bonded to the underlayer by torching.

Important:
Cannot be used in flame-free zones.

⚠️ Warning

Important:

Cap sheet should run in the same direction as the underlayer, and be off-set from the underlayer, so as not to impede drainage/falls. No small sections should be used.

BAB01D~1

8.3 Torch-on fully bonded root resistant capping sheets

PLANT E 42, PLANT E and SMARAGD.

Bond: Full over whole surface, with no air pockets.

Laying top layer: Fully bonded to the underlayer by torching.

Important:
Cannot be used in flame-free zones, unless hot air welding.

⚠️ Warning

Only to be used in torch-safe zones. See Section 1.5

BA4AC3~1

8.4 Self-adhesive capping sheets

KSO SN, KSO ALP SN and KSO-P SN, hot air welded.

Bond: Full over whole surface, with no air pockets.

Laying top layer: Cold applied and fully bonded to the underlayer by hot air welding.

⚠️ Warning

Important:

Bauder Activator-Primer (Canister), must be applied to the underlayer prior to installation of the self-adhesive capping sheet.

Must be used in flame-free zones and can be used in torch-safe zones.

BAUDER~2